BAUDOUIN 250 kVA 3 Phase Silent Diesel Generator
The Baudouin 250 kVA 3 phase silent diesel generator represents the pinnacle of heavy-duty industrial standby engineering, purpose-built to sustain critical infrastructure, massive corporate complexes, multi-tenant commercial parks, and intensive agricultural operations through prolonged power grid blackouts. Leveraging over a century of French marine and military-grade engineering heritage, this massive commercial backup power plant provides an elite level of reliability and structural stamina unmatched in its class.
Encased in a custom-engineered, heavy-gauge sound-attenuated weatherproof canopy, this industrial standby generator isolates and reduces severe combustion noise down to a localized 72–75 dB at 7 meters. This makes it an ideal, compliant choice for high-density business parks, medical clinics, and upscale urban developments with strict environmental acoustics regulations.
Detailed Engineering & Performance Breakdown
Premium Marine-Derived Powertrain & Alternator Performance
At the core of this heavy three-phase diesel generator sits the turbocharged and aftercooled Baudouin 6M16G275/5 diesel engine. This massive 9.726-liter displacement, 6-cylinder inline powerhouse utilizes an electronic governor for microscopic frequency regulation under intense block loading. The engine is coupled directly to a top-tier brushless, synchronous alternator (such as StromerPower or Leroy Somer) featuring IP23 ingress protection, H-class winding insulation, and an Automatic Voltage Regulator (AVR) to sustain steady-state voltage margins within ±0.5%, shielding complex corporate IT servers and medical hardware from transient surges.
Automation via Intelligent SmartGen / Deep Sea Controls
For instantaneous, unassisted facility changeover during a utility outage, the generator incorporates an intelligent digital management suite (typically the SmartGen HGM6120N or DSE 7310 electronic controller). The unit features auto-mains failure (AMF) programming that continually tests engine safety variables, low oil pressures, high engine temperatures, and overcurrent conditions. Coupled with a heavy-duty, multi-pole 250kVA automatic transfer switch (ATS) installation, the setup autonomously initiates, balances, and routes clean backup electricity to the primary facility distribution board in under 10 seconds.
Fuel Efficiency & Long-Range Industrial Runtime Math
Engineered for highly optimized thermal performance, the 6-cylinder Baudouin architecture offers exceptionally clean, cost-efficient fluid mechanics at a fixed 1500 RPM (50Hz) standard:
50% Prime Load: ~28.3 Liters / hour
75% Prime Load: ~42.2 Liters / hour
100% Prime Load: ~56.9 Liters / hour
Outfitted with an integrated, long-range bunded base fuel tank holding upwards of 540 liters, this heavy-duty commercial standby plant safely guarantees up to 12.8 hours of continuous, unrefueled operation at a consistent 75% load capacity.
Technical Specifications Summary Matrix
Standby Rating (ESP): 275 kVA / 220 kW (Emergency standby backup limits, no continuous overload)
Prime Rating (PRP): 250 kVA / 200 kW (Continuous variable load operations, 10% overload allowed 1hr/12hr)
Frequency & Speed: 50 Hz @ 1500 RPM (Three Phase / 400V / 230V)
Safety Protocols: Auto-shutdown on high water temperature, critical low oil pressure, battery charger fail, and over-speed limits
Dimensions & Massive Construction: ~3400mm (L) x 1200mm (W) x 2150mm (H) with a dry chassis weight of roughly 3,410 kg